DI-STRIP Protector FI / LS Standard DIN 49 440 (DIN)

back  
 
DI-STRIP Protector FI / LS Socket Strips and Power Distribution Units
 
 


Protector FI / LS
- RCCB and circuit breaker
- Provides a combination of user, overload and short circuit protection
- Residual operating current Ig = 30 mA for alternating and intermittent
  fault directcurrent
- Circuit breaker 16 A
- Tripping characteristic type B, 2-pole
- 19” installation option (with length 483 mm)
- Socket rotation: 45°
- Cable: H05VV-F 3G 1.5 mm²
- Moulded right angle plug

Material / Finish
Casing: closed sheet steel extrusion, zincplated, powder-coated texture
Plastic parts: Vampamid 6 0024 VO (UL94), recyclable
Internal conductor: full-length bus bar, brass

Dimensions
Socket spacing: 50 mm
Height: 78 mm
Casing width: 44.4 mm (= 1 HU)
Cable: 2.5 m

Approvals
- CE Label in accordance with low voltage directive
  2006/95/EEC EMC Directive 2006/108/EEC
- Innova-GS
- CB-scheme

Color
RAL 7035 light-grey
Plastic parts: RAL 7035 light-grey

Load rating
100-240 Vac/16 A

Supply schedule
1 socket strip
2 mounting brackets
2 19” mounting brackets (additional with 19” installation option)
 