- For protecting against transient overvoltages
from the mains, which,
for example, are
caused by switching machines on and off.
- With critical overvoltages the mains is
separated.
- Once the safety arrester has been triggered
the green function display
goes out. The
socket strip can then no longer be used.
Send the socket strip
to the manufacturer for
the safety arrester to be replaced!
The safety effect
of the type 3 test category
and requirements category “D” is to protect
the
equipment, i.e. precision protection.
The protection devices of the test and requirements
categories 1 and 2 and B
and C
must be preconnected in the building installation
to ensure optimum protection.
- 19” installation option (with length 483 mm)
- Socket rotation: 45°
- Cable: H05VV-F 3G 1.5 mm²
- Moulded right angle plug
Material / Finish
Casing: closed sheet steel extrusion, zincplated,
powder-coated texture
Plastic parts: Vampamid 6 0024 VO (UL94),
recyclable
Internal conductor: full-length busbar,
brass
Dimensions
Socket spacing: 50 mm
Height: 45.5 mm
Casing width: 44.4 mm (= 1 HU)
Approvals
- CE Label in accordance with low voltage
directive
2006/95/EEC
EMC Directive 2006/108/EEC
- Innova-GS
- CB-scheme
- VDE
Color
Final digit of order number .1:
RAL 7035 light-grey
Final digit of order number .6:
Casing, RAL 2003, pastel orange
Plastic parts: RAL 7035 light-grey
Technical data
Test category: Type 3
- In acc. with DIN EN 61643-11
Feature class: D
- In acc. with VDE 0675-6
Mains voltage: 230 VAC
Nominal current: max. 16 A
Cut-off discharge current (8/20 ?s): 10 kA
Reaction time: ‹ 25 ns
Protection level
(with 100 A varistor peak current):
- L with respect to N: ‹ 800 V
- L/N with respect to PE: ‹ 1500 V
Supply schedule
1 socket strip
2 mounting brackets
2 19” mounting brackets (additional with
19” installation option) |
 |
 |
 |
|
|