- The “Safety Standard” models consist of a
combined overvoltage
protection/mains
filter element.
- For protecting against transient overvoltages
from the mains, which,
for example, are
caused by switching machines on and off.
- With critical overvoltages the mains is
separated.
- Once the safety arrester has been triggered
the green function display goes out.
The socket
strip can then no longer be used. Send the
socket strip to the
manufacturer for the safety
arrester to be replaced!
- The safety effect of the type 3 test category
and requirements category “D”
is to protect
the equipment, i.e. precision protection.
The protection devices
of the test and requirements
categories 1 and 2 and B and C
must be
preconnected in the building installation
to ensure optimum protection.
- High-frequency glitches are generally
caused by switching processes in an
operation
from 100 kHz to 5MHz.
- This high-frequency rate overloads the
mains frequency and affects adjacent electronic
equipment. The mains filter attenuates
this high-frequency rate.
- The attenuation behaviour is harmonized with
the typical interference spectrum.
- 19” installation option (with length 483 mm)
- Socket rotation: 45°
- Cable: H05VV-F 3G 1.5 mm²
- Moulded right angle plug
Material / Finish
Casing: closed sheet steel extrusion, zincplated,
powder-coated texture
Plastic parts: Vampamid 6 0024 VO (UL94),
recyclable
Internal conductor: full-length busbar,
brass
Dimensions
Socket spacing: 50 mm
Height: 45.5 mm
Casing width: 44.4 mm (= 1 HU)
Cable: 2.5 m
Approvals
- CE Label in accordance with low voltage
directive
2006/95/EEC
EMC Directive 2006/108/EEC
- Innova-GS
- CB-scheme
- VDE
Color
Final digit of order number .1:
RAL 7035 light-grey
Final digit of order number .6:
Casing, RAL 2003, pastel orange
Plastic parts: RAL 7035 light-grey
Technical data
Mains voltage: 230 VAC
Nominal current: max. 16 A
Cut-off discharge current (8/20 ?s): 10 kA
Reaction time: ‹ 25 ns
Protection level
(with 100 A varistor peak current):
- L with respect to N: ‹ 800 V
- L/N with respect to PE: ‹ 1500 V
Overvoltage protection
- Test category: Type 3
in acc. with DIN EN61643-11
- Feature class: D
- In acc. with VDE 0675-6
Mains filter
- In acc. with VDE 0565 (EN 60939)
Supply schedule
1 socket strip
2 mounting brackets
2 19” mounting brackets (additional with
19” installation option) |
 |
 |
 |
|
|