■ With fixed 19" installation on the front and
rear
■ For components in acc. with IEC 297-3
■ Door opening angle, 180°
■ For installing:
- 19" components on the front and rear
- Equipment with max. construction width of
450 mm
- Installation accessories
■ Jumpering space
At the front: 73 mm
■ Load rating
5000 N static
■ Protection rating
IP 55
■ Tests
- Earthing in acc. with VDE 0100 T 540
- Vibration test in acc. with MIL-STD 810 E
- IP test in acc. with DIN 40 050 / IEC 529
■ Material/ Finish
- Basic rack, extruded aluminum, polished
- Corner piece, die-cast aluminum, polished
- Covers, zinc-passivated sheet steel, powdercoated
texture
- Doors, sheet steel, powder-coated texture,
glass infill, front door,
single safety glass
panel, 4 mm
- Multifunctional braces and 19" extrusions,
sheet steel, zinc-passivated
■ Color
Visible surface of the cover
RAL 7035 light gray
■ Supply schedule
1 basic frame
4 19" sheet steel angular extrusions with
mounting holes
2 multifunctional braces for cable clamping
and universal mounting options
1 top cover, closed, IP 55
1 front door, single, single safety glass panel,
with handle and mounting
for cylinder lock,
IP 55
1 rear panel with quick connectors, IP 55
2 side panels with quick connectors, IP 55
1 bottom cover, closed, IP 55
4 leveling feet (0-25 mm)
■ How supplied
- Assembled
■ Note: Rack suites
To create a rack suite with "n" racks, you
require:
(n-1) racks without side panels
1 rack with side panels
In a rack suite, per connection you require a
set of suite connectors BN 01.130.935.7.
IP 55 sealing frame on request! |
 |
 |
 |
|
|