Knürr HighPower RM® back  
 
Knürr HighPower - this design is without  current distribution - Power Distribution Unit   Knürr DI-STRIP ® High Power
• with remote-metering module
• Particularly flat casing profile
- this allows full accessibility to 19 " level at 600mm wide server cabinets
- Large clear LCD display
- Meets stringent EMC requirements for noise interference and noise emission
- Accuracy <2%
- Adjustable up to 3 thresholds and out of balance control
• rotating display in 90 ° increments
• automatic reduction of the backlight
• Protocols: HTTP, SNMP, Syslog

Technical Description
• Free access to 19" level also with 600-mm-wide racks by flat construction method
• Individual security of the outlets (groups with 10 A)
• Subdivision of the outlets in to groups with max. 20 A per group
• Modular enlargement in the rack possibly by installation of the PDUs without tools
• With a large well-arranged LCD display
• Display of true RMS value of the alternating current input
• Rotation of the LCD display in 90° intervals
• Display switchable between dark and bright
• Signaling of load changes
• Automatic reduction of background lighting
• Conforms to the most stringent EMC requirements (interference resistance:
  criterion A, electromagnetic interference: class B)
• Other designs (e.g. Sheet J outlets) on enquiry
• IEC 320 sockets (Sheet J; Sheet F)
• Sheet J and Sheet F are secured in groups with 20 A hydraulic-magnetic
  circuit breaker
• 1 or 5 Sheet F outlets are secured by resettable thermal circuit breakers
  according to IEC60934
• Feed: IEC32 AÖ191 / 10 6 mm²
• With plug IEC60309 1Ph/N/PE 6h blue or 3Ph/N/PE 6h red

Data Interface
• The socket strip can be integrated into a network using a RJ45 plug
• It can be accessed remotely using a web browser, a special software
  is not necessary.
• 3 threshold values as well as an unbalanced load warning can be set variably.
• The module offers access for up to 5 users or administrators, access is
  password protected.
• The software shows the name as well as the location of the PDU, both can
  be entered by an administrator.
• The user can set a static IP address or access using DHCP.
• Firmware updates can be done using a Web browser.
• Supported protocols: HTTP, SNMP (Traps, SET, GET), Syslog

Approvals
• CE label in accordance with the low potential guidline 2006/95/EC
• EMC guideline 89/336/ECC
 