Tecoras Heat Exchanger Cabinet   back  
 
Tecoras Outdoor Rack - Outdoor Cabinet Heat Exchanger Cabinet
 
Quick Download:
Tecoras Outdoor Systems
(PDF, 1.4 MB)
 

■ Double-wall outdoor enclosure
■ With EMC sealing
■ With air-to-air heat exchanger with 1 48 VDC fan for the outer and inner air circulation, thermostat controlled
■ Active vented and ribbed side and rear panels
■ All bolting and connection elements situated inside
■ Hinged solar protection roof
■ Doorstop changeable
■ Door with lock and release lever for extrusion half-cylinder with saw protection, triple interlocking system, closed
■ Door lock-in, lock-out with opening angles of 90° and 135°
■ Sound pressure level less than 55 dB(A) at a distance of 1 m in accordance with ISO 7779

For the installation of
■ Components in accordance with IEC 297-3 (19") or IEC 917 (metric)
■ Non-standard equipment with max. installation width of 535 mm

Load rating
■ 4000N static

Standards
■ Built-in units in accordance with IEC 297-3 (19") and IEC 917 (metric)
■ Earthing in accordance with VDE 0100
■ IP protection in accordance with EN 60529
■ Sound pressure in accordance with ISO 7779

Degree of protection
■ IP 55

Tests
■ Environmental test in accordance with IEC 68-2-1, IEC 68-2-2, IEC 68-2-5, IEC 68-2-56
■ Vibration tested in accordance with IEC 68-2-6
■ Earthquakeproof to zone 4 in accordance with Telcordia GR-63-CORE
■ Shielding attenuation in accordance with IEC 61 587-3 at least 25 dB

Material / Finish
■ Basic rack: extruded aluminium AlMgSi0,5
■ Corner piece: die-cast aluminium
■ Internal cover panel: aluminium AlMg 3, 1.5 mm thick, chrome-plated
■ External cover panel: aluminium AlMg 3, 2 mm thick, chrome-plated, powder-coated front quality in accordance with GSB International, coarse textured
■ Plinth frame: zinc passivated sheet steel
■ Plinth cover panel: hot-galvanized (zinc-coated) sheet steel DX51 D + Z 140, 1.5 mm
Colour
■ RAL 7035 light grey

Supply schedule
1 Basic rack with base and 2 corner extrusions
1 Double-wall, ribbed rear cover panel with internal air baffle
2 Double-wall, ribbed side cover panels with internal air baffle
1 Fan module with 2 fans 48 V DC, thermostat controlled for air circulation inside/outside
1 Solar protection roof
1 Front door, opens to the right, closed
1 Plinth frame 210 mm high, with 2 side cover panels, with 1 front and 1 rear removeable panel
1 Earthing set
1 Cable entrance panel, closed

How supplied
■ assembled

Princible of the integrated heat exchanger
■ Integration of the heat transfer systemin the outer panels
■ Installation of fans and electronic control in the roof
■ Optimal layout of air intake and air outflow causes lowest wind intake and elimination of airflow disruption

nach oben top

 
 
Tecoras Heat Exchanger Cabinet Order Number
width installation width depth useable depth height installation height h max. sec. cooling capacity  
B [mm] b [mm] T [mm] t [mm] H [mm] [U] [mm] [W/K] *  
700 535 405 330 1000 19 850 28 01.900.003.1
1180 22 1030 40 01.900.005.1
1400 28 1250 43 01.900.007.1
1580 32 1430 48 01.900.009.1
705 630 1000 19 850 48 01.900.023.1
1180 22 1030 55 01.900.025.1
1400 28 1250 58 01.900.027.1
1580 32 1430 63 01.900.029.1
1335 1070 405 300 1000 19 850 55 01.900.401.1
1180 22 1030 68 01.900.402.1
1400 28 1250 70 01.900.403.1
1580 32 1430 78 01.900.404.1
705 600 1000 19 850 73 01.900.411.1
1180 22 1030 85 01.900.412.1
1400 28 1250 88 01.900.413.1
1580 32 1430 98 01.900.414.1


* The max. specific cooling capacity refers to the difference between the intake temperature of the ambient air and the return temperature of the interal air.
 
     