Tecoras Street Cabinet HEC with Side Door   back  
 
Tecoras Street Cabinet HEC, with Side Door and Air-to-Air Heat Exchanger
 
Quick Download:
Tecoras Outdoor Systems
(PDF, 1.4 MB)
 

■ Single-wall cabinet with air-to-air heat exchange integrated in the rear panel with 1 48 VDC fan for inner and 1 for outer circulation, thermostat controlled
■ All bolting and connection elements situated inside
■ Hinged solar protection roof
■ 1 Front door and 1 side door, closed with lock and release lever for extrusion half-cylinder with saw protection, triple interlocking system
■ Door lock-in, lock-out with opening angles of 90° and 135°
■ Sound pressure level less than 55 dB(A) at a distance of 1 m in accordance with ISO 7779

Variants
Type 1
■ With external cover panels of aluminium AlMg3, 2 mm ( order number 01.917.XXX.1 )
Type 2
■ With external cover panels of hot-galvanized sheet steel DX 51 D + Z 140, 1.5 mm ( order number 01.918.XXX.1 )

For the installation of
■ Components in accordance with IEC 297-3 (19") or IEC 917 (metric)
■ Non-standard equipment with max. installation width of 535 mm for DIN rail and assembly panel mounting in the main installation space

Load rating
■ 4000N static

Standards
■ Built-in units in accordance with IEC 297-3 (19") and IEC 917 (metric)
■ Earthing in accordance with VDE 0100
■ IP protection in accordance with EN 60529
■ Sound pressure in accordance with ISO 7779

Degree of protection
■ IP 55

Tests
■ Environmental test in accordance with IEC 68-2-1, IEC 68-2-2, IEC 68-2-5, IEC 68-2-56
■ Vibration tested in accordance with IEC 68-2-6
■ Earthquakeproof to zone 4 in accordance with Telcordia GR-63-CORE

Material / Finish
Type 1
■ Basic rack: extruded aluminium AlMgSi0,5
■ Corner piece: die-cast aluminium
■ Solar protection roof: aluminium AlMg3, 2 mm
■ External cover panels of aluminium AlMg3, 2 mm
■ Ribbed rear panel (heat transfer system): aluminium AlMg3, 2 mm
■ Dividing wall: sheet steel 1.0 mm, hot-galvanized (zinc-coated)
■ Chrome-plated, powder-coated front quality in accordance with GSB International, coarse textured
Type 2
■ Basic rack: extruded aluminium AlMgSi0,5
■ Corner piece: die-cast aluminium
■ Solar protection roof : aluminium AlMg3, 2 mm
■ External cover panels of hot-galvanized (zinc-coated) sheet steel 1.5 mm
■ Ribbed rear wall (heat transfer system): aluminium AlMg3, 2 mm
■ Dividing wall: sheet steel 1.0 mm, hot-galvanized (zinc-coated)
■ Powder-coated front quality in accordance with GSB International, coarse textured
Colour
■ RAL 7035 light grey

Supply schedule
1 Basic rack with cover and base
1 Double-wall ribbed rear wall with air baffle
1 Fan module with 2 fans, thermostat controlled
1 Side panel
1 Solar protection roof
1 Front door, opens to the right, closed
1 Side door, opens to the left, closed
1 Dividing wall
1 Earthing set

How supplied
■ assembled

Principle of the integrated heat exchanger
■ Integration of heat transfer system in the rear panel
■ Installation of fans and electronis control in the roof
■ Optimal layout of air intake and air aoutflow causes lowest wind intake and elimination of airflow disruption

nach oben top

 
 
  Tecoras Street Cabinet with single-winged front door, closed,
with side door, closed, with air-to-air heat exchanger
Order Number
width installation width depth useable depth type height installation height h max. sec. cooling capacity  
B [mm] b [mm] T [mm] t [mm]   H [mm] [U] [mm] [W / K] *  
740 635 375 310 1 780 14 630 13 01.917.220.1
1000 19 850 15 01.917.222.1
1180 23 1030 18 01.917.224.1
           
         
         
475 410 1 780 14 630 13 01.917.230.1
1000 19 850 15 01.917.232.1
1180 23 1030 18 01.917.234.1
      
     
     


* The max. specific cooling capacity refers to the difference between the intake temperature of the ambient air and the return temperature of the interal air.
 
     
  Print page  
     
  nach oben top