Tecoras Wall Case HEC, Air/Air Heat Exchanger   back  
 
Tecoras Wall Case HEC, Air/Air Heat Exchanger
 
Quick Download:
Tecoras Outdoor Systems
(PDF, 1.4 MB)
 

■ Double skinned outdoor wall enclosure with air-air heat exchanger integrated in the side panels for installing non-standard equipment with installation widths of 305 to 485 mm for mounting of DIN rails and mounting panels and 19" components ( only for enclosure widths 650 mm)
■ Vented and ribbed side panels
■ 1 Fan module with 2 fans 48 VDC for external and internal circulation, thermostatic controlled
■ With solar protection roof
■ Front door closed, hinged on the right or left

Load rating
■ 500 N static

Degree of protection
■ IP 55

Principle of the integrated heat exchanger
■ Integration of the heat exchanger in the side panels
■ Installation of fan and electronic control board in the roof for maximum volume use
■ Optimised layout of air intake and air exhaust results in low wind influx and exclusion of the air short circuit
■ Sound pressure level, less than 55 dB (A) at a distance of 1 m in accordance with ISO 7779

Material
■ Aluminium AIMg 3, colourless chrome-plated, 3 mm
■ Heat exchanger panel with ribs of aluminium, 2 mm
■ External covers, aluminium AIMg3, 2 mm

Finish / Colour
■ Powder-coated, RAL 7035 light-grey, outdoor quality in accordance with GSB International, coarse textured

Supply schedule
1 Wall enclosure with front door
2 Double skinned ribbed side panels with internal channel plate
1 Solar protection roof
1 Fan module with 2 fans 48 VDC, mounted in the top cover
1 Closed cable entry panel in the bottom cover
1 Earthing set

How supplied
■ assembled

Please note
The internal fan reduces the useful height h by 45 mm

nach oben top

 
 
Tecoras Outdoor Wall Enclosure,
with Air/Air Heat Exchanger
Order Number
height width depth max. sec. cooling capacity  
H [mm] h [mm] B [mm] b [mm] T [mm] t [mm]** [W / K]*  
700 540 550 385 345 290 35 01.914.500.1
700 540 650 485 345 290 35 01.914.502.1
385 445 390 40 01.914.510.1
900 740 550 385 345 290 40 01.914.504.1
900 740 650 485 345 290 40 01.914.506.1
445 390 45 01.914.508.1


* The max. specific cooling capacity refers to the difference between the intake temperature of the ambient air and the return temperature of the interal air.
 
     
  Print page  
     